InsightCM 26.2 Cannot Communicate With PI Historian After Upgrade

Issue Details

After upgrading to InsightCM 26.2, communication with the PI Historian no longer works. Why is this happening?

 

Solution/Procedure

This issue occurs because the server has an older version of PI Asset Framework (AF) Client installed. InsightCM 26.2 requires PI AF Client 2024 R2 Patch 1 or later. To restore communication, upgrade PI AF Client on the InsightCM server.

1. Confirm the installed version: open Control Panel > Programs and Features and locate PI AF Client. If the version is earlier than 2024 R2 Patch 1, continue with the next step.

2. Create a checkpoint (snapshot), full backup, or restore point of the server before making changes.

3. Install or upgrade to PI AF Client 2024 R2 Patch 1.

4. The installation should restart the InsightCM service automatically. However, we recommend rebooting the server if possible.

5. Validate the connection: in InsightCM, go to Navigation Menu > System > Historian, click the Action Menu, select Query Points, and enter *.

PI H.png

6. If the query returns the PI points, InsightCM is communicating with the PI Historian again.

 