The Assurance Monitoring System is equipped with both TCP/IP and RTU (RS485) Modbus output options. Each Assurance device operates as a slave only.

Modbus Protocol Features

When using the RTU protocol, the Assurance Monitoring System will answer to a master query only if the query contains the same slave address as defined on the Assurance device. The permitted addresses range from 1 to 254 (0x01 to 0xFE), and there should be no controllers with the same address on the same line.

Feature

Description

Supported Functions

Read Input Register (0x03)

Cyclical Redundancy Check (CRC)

16-bit value calculated by both devices. Error message displayed when values are not equal.

Table 4. Default Modbus Settings

Parameter

Default Value

IP Address

192.168.1.222

TCP Port

502

Modbus ID

1

Baud Rate

115200

Parity

None

Stop Bits

1


The Modbus settings on the Assurance Monitoring System can be configured using a serial console, such as PuTTY. The Assurance System can be connected to a laptop with the serial console software using the DB9 serial port located on the backside of the Assurance faceplate.

Below is a list of commands that may be useful in configuring the Assurance System.

Example Command

Result

showsettings

Shows the current Modbus settings

mbid 1

Sets the Modbus ID to 1

baudrate 9600

Sets the baud rate to 9600

stopbits 1

Sets the number of stop bits to 1

mbtcpport 502

Sets the TCP Port to 502

ipaddr 192.168.1.100

Sets the IP address to 192.168.1.100

subnet 255.255.255.0

Sets the subnet mask to 255.255.255.0

gateway 192.168.1.1

Sets the default gateway to 192.168.1.1

Termination Resistance

The Assurance Monitoring System features a block of DIP switches (SW1) to set the desired termination resistance for Modbus RS485 communication. SW1 is located on the back side of the Assurance faceplate assembly adjacent to the Modbus RS485 termination points. The below table outlines the available termination resistor settings with corresponding DIP switch configurations.

Termination Resistance Value

Switch 1

Switch 2

Switch 3

Switch 4

No Termination Resistance

Off

Off

Off

Off

60 Ohms

On

On

Off

Off

120 Ohms

On

Off

Off

Off

Address Declarations

Name

Value Type

Value Unit

Register Type

Address (Base 0)

Supported Functions

Shaft Voltage RMS

Float

Volts RMS

Input Register

30000

Read Input Register

Shaft Voltage 0–Peak

Float

Volts 0–Peak

Input Register

30002

Read Input Register

Shaft Voltage DC

Float

Volts DC

Input Register

30004

Read Input Register

Ground Current RMS

Float

Amps RMS

Input Register

30006

Read Input Register

Ground Current 0–Peak

Float

Amps 0–Peak

Input Register

30008

Read Input Register

Ground Current DC

Float

Amps DC

Input Register

30010

Read Input Register

Rope Status

Integer

Flag

Input Register

30012

Read Input Register

Rope Status Channel Interpretation

Integer Output

Interpretation

3

No Rope Fault (Normal)

2

Ground Rope Fault

1

Meter Rope Fault

0

Meter Rope and Ground Rope Fault

Was this article helpful?
0 out of 0 found this helpful