This manual describes the installation of the Cutsforth Shaft Grounding Assembly.
The following parts are included in the Shaft Grounding Assembly installation package:
1 Shaft Grounding Assembly Part # EGSA-210 |
|
2 Shaft grounding ropes Part # EGHK-205 |
|
1 Attachment arm pipe Part # EGSM-012 |
|
1 Rope guide spacer (1/16 in thick) |
|
2 Elbow assemblies Part # EGSA-004 |
|
1 Connector plate and hardware Part # EGSM-009 |
|
1 High-Frequency Drain Kit Part # EGSA-303 |
|
-
Welder, TIG preferred (for Shaft Grounding Assembly only)
-
1/2 in hex wrench socket
-
9/16 in socket wrench
-
1/4 in hex key wrench
-
3/16 in hex key wrench
-
Drill
-
5/16 in-18 tap
-
Letter F drill bit
-
Wire cutters
-
Wire strippers
-
Wire crimpers
-
Tape, banding, and/or clamps (for Shaft Grounding Assembly only)
-
The shaft must be fully coupled.
-
The generator and turbine bearing caps in the load compartment must be fully installed.
-
The condition of the shaft at the Shaft Grounding Assembly installation location must be documented by photo or video. If the shaft is still rotating, use a strobe to capture a video of the shaft condition. To facilitate a robust electrical contact for the shaft grounding system, make sure that the shaft surface is free of grooving, pitting, oxidation, and contamination.