This section provides detailed technical information on the Generator Field Monitoring System capabilities and legal information.

Monitored Lines and Bandwidths

Standard Data Collection

Monitored Line

Bandwidth

Attenuation Ratio

Ground Current

1 MS/s or 222 kHz

30 A : 10 V

Shaft Voltage

1 MS/s or 222 kHz

100 V : 10 V

Exciter Shaft Voltage

1 MS/s or 222 kHz

100 V : 10 V

Rotor Flux

100 kS/s or 22.2 kHz

100 V : 10 V

How Average and Peak Values Are Calculated

  • Average voltages and currents are calculated on the samples taken during each snapshot as the sum of (x)/N, where x is the array of samples acquired, and N is the number of samples.

  • Zero-to-peak voltages and currents are calculated on the samples taken during each 0.02 second period by the following formula:

    Peak-Values-1-2080.png
  • The longer-term averages are calculated by accumulating averages for the specified period. They are then reset in preparation for the next calculation. The formula used is as follows:

    Peak-Values-2-2080.png

Related Documents

Document Name

Document Number

Shaft Grounding System Operations Manual

Series 1: EZDP-2007

Series 2: EZDP-2035

Series 3: EZDP-2068

Generator Field Monitoring System Installation Planning Guide

EZDP-2090

Generator Field Monitoring System Wiring Diagram

Refer to Product Part Number (e.g., EAMA-002, EAMA-201)

InsightCM Installation Manual

Refer to the InsightCM installation instructions on the Cutsforth Support Webpage

Activating InsightCM Server License

Refer to the InsightCM licensing instructions on the Cutsforth Support Webpage