Related Products: |
EGSA-013, EGSA-015, EGSA-210, EGSA-220, EAMA-001, EAMA-003 |
Related Documents: |
EZDP-2100 |
Type: |
operations, reference information |
Keywords/Labels: |
shaft voltage RMS output, exciter shaft voltage RMS output, ground current RMS output, unit status, |
Summary: |
This topic provides output values for shaft voltage, exciter shaft voltage, and ground current RMS. |
Shaft Voltage (V) |
Conditioned Voltage (V) |
4-20 mA Output |
---|---|---|
0 |
0 |
4 |
25 |
2.5 |
8 |
50 |
5 |
12 |
75 |
7.5 |
16 |
100 |
10 |
20 |
Shaft Voltage (V) |
Conditioned Voltage (V) |
4-20 mA Output |
---|---|---|
0 |
0 |
4 |
25 |
2.5 |
8 |
50 |
5 |
12 |
75 |
7.5 |
16 |
100 |
10 |
20 |
Shaft Voltage (V) |
Conditioned Voltage (V) |
4-20 mA Output |
---|---|---|
0 |
0 |
4 |
12.5 |
2.5 |
8 |
25 |
5 |
12 |
37.5 |
7.5 |
16 |
50 |
10 |
20 |
In the following table, the shaded cells apply only when the optional Exciter Shaft Contact Assembly (SCA) is installed.
4-20 mA Output (± 0.5 mA) |
Condition |
Description or Recommended Action |
||
---|---|---|---|---|
4 |
Normal, generator online |
Alert: Generator online. Not a fault condition. |
||
|
SGA ground rope |
SGA meter rope |
SCA exciter rope |
6-12 mA = Rope status array |
6 |
Stepped Up |
Normal |
Normal |
Rope Fault: SGA ground rope |
7 |
Normal |
Stepped Up |
Normal |
Rope Fault: SGA meter rope |
8 |
Normal |
Normal |
Stepped Up |
Rope Fault: SCA exciter rope |
9 |
Stepped Up |
Stepped Up |
Normal |
Rope Fault: SGA ground rope and SGA meter rope |
10 |
Stepped Up |
Normal |
Stepped Up |
Rope Fault: SGA ground rope and SCA exciter rope |
11 |
Normal |
Stepped Up |
Stepped Up |
Rope Fault: SGA meter rope and SCA exciter rope |
12 |
Stepped Up |
Stepped Up |
Stepped Up |
Rope Fault: SGA ground rope, SGA meter rope, and SCA exciter rope |
13 - 20 |
Not a valid output. |
|