Technical Specifications (EZDP-2104)

Related Products:

EGSA-310, EGSA-320, EAMA-005

Related Documents:

EZDP-2104

Type:

Operations, Specifications

Keywords/Labels:

enclosure, power supply, digitizers, electromagnetic compatibility, environmental

Summary:

This document provides the technical specifications for Generator Field Monitoring.

Technical Specifications

Monitoring System Enclosure

Catalog Number

AxBxC (in.)

Stainless Steel Type

Panel Size DxE (in.)

F (in.)

Clamps Qty.

A24H2006SSLP

24.00 x 20.00 x 6.00

304

21.00 x 17.00

3.00

5

Enclosures-Diagram.png

Specifications:

  • UL 508A Listed; Type 3R, 4, 4X, 12; File No. E61997

  • cUL Listed per CSA C22.2 No 94; Type 3R, 4, 4X, 12; File No. E61997

  • NEMA/EEMAC Type 3R, 4, 4X, 12, 13

  • CSA File No. 42186: Type 4, 4X, 12

  • IEC 60529, IP66

  • Meets NEMA Type 3RX requirements

AC Power Supply Requirements

Plant-supplied Power Source

120 V, 60 Hz AC or 240 V, 50 Hz AC

Circuit Breaker

Internal 120 V, 5 A

Circuit Draw Under Normal Usage

Approximately 0.6 A

Digitizers

NI-9775

Range

± 10 V

Sample Rate

20 MS/s

Resolution

14-bit

Manufacturer's Datasheet

http://www.ni.com/pdf/manuals/377101b_02.pdf

NI-9215

Range

± 10 V

Sample Rate

100 kS/s

Resolution

16-bit

Manufacturer's Datasheet

http://www.ni.com/pdf/manuals/373779a_02.pdf

Safety Standard

This product is designed to meet the requirements of the IEC 61010-1, EN 61010-1 and UL 61010-1, CSA 61010-1 standards of safety for electrical equipment for measurement, control, and laboratory use.

Electromagnetic Compatibility

This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use:

EN 61326 (IEC 61326)

Class A emissions; Basic immunity

EN 55011 (CISPR 11)

Group 1, Class A emissions

AS/NZS CISPR 11

Group 1, Class A emissions

FCC 47 CFR Part 15B

Class A emissions

ICES-001

Class A emissions

CE Compliance

Meets the essential requirements of applicable European Directives, as amended for CE marking, as follows: 2006/95/EC, Low-Voltage Directive (safety); 2004/108/EC, Electromagnetic Compatibility Directive (EMC)

Environmental

Storage Temperature

-40 °C to 85 °C (-40 °F to 185 °F)

Operating Temperature

-40 °C to 70 °C (-40 °F to 158 °F)

Storage Humidity

5% RH to 95% RH, noncondensing

Operating Humidity

10% RH to 90% RH, noncondensing

Maximum Altitude

5,000 m (16,400 ft)

Do you need more help?

Was this article helpful?
0 out of 0 found this helpful