This section provides detailed technical information on the Generator Field Monitoring System capabilities and legal information.
Standard Data Collection
Monitored Line |
Bandwidth |
Attenuation Ratio |
---|---|---|
Ground Current |
1 MS/s or 222 kHz |
30 A : 10 V |
Shaft Voltage |
1 MS/s or 222 kHz |
100 V : 10 V |
Exciter Shaft Voltage |
1 MS/s or 222 kHz |
100 V : 10 V |
Meter Rope Wear Indicator |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Ground Rope Wear Indicator |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Exciter Meter Rope Wear Indicator |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Rotor Flux |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Burst Mode
Monitored Line |
Bandwidth |
Attenuation Ratio |
---|---|---|
Ground Current |
20 MS/s or 500 kHz |
30 A : 10 V |
Shaft Voltage |
20 MS/s or 500 kHz |
100 V : 10 V |
Exciter Shaft Voltage |
20 MS/s or 500 kHz |
100 V : 10 V |
Meter Rope Wear Indicator |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Ground Rope Wear Indicator |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Exciter Meter Rope Wear Indicator |
100 kS/s or 22.2 kHz |
100 V : 10 V |
Rotor Flux |
100 kS/s or 22.2 kHz |
100 V : 10 V |
-
Average voltages and currents are calculated on the samples taken during each snapshot as the sum of (x)/N, where x is the array of samples acquired, and N is the number of samples.
-
Zero-to-peak voltages and currents are calculated on the samples taken during each 0.02 second period by the following formula:
-
The longer-term averages are calculated by accumulating averages for the specified period. They are then reset in preparation for the next calculation. The formula used is as follows: