Technical Specifications

Monitoring System Enclosure

Catalog Number

Dimensions (in. (mm))

Stainless Steel Type

CSD16168SS6-MODS

16.0 (406) x 16.0 (406) x 8.0 (203)

316

 

EnclosureSpecifications-2078.png

Specifications:

  • UL 508A Listed; Type 3R, 4, 4X, 12; File No. E61997

  • cUL Listed per CSA C22.2 No 94; Type 3R, 4, 4X, 12; File No. E61997

  • NEMA/EEMAC Type 3R, 4, 4X, 12, 13

  • CSA File No. 42186: Type 4, 4X, 12

  • VDE IP66

  • IEC 60529, IP66

  • Meets NEMA Type 3RX requirements

EXMC-001: Optional sunshield for outdoor installations

EnclosureSpecsOptional2078.png
 

AC Power Supply Requirements

Plant-supplied Power Source

120 V, 60 Hz AC or 240 V, 50 Hz AC

Circuit Breaker

Internal 120 V, 5 A

Circuit Draw Under Normal Usage

Approximately 0.6 A

 

Digitizers

NI-9775

Range

± 10 V

Sample Rate

20 MS/s

Resolution

14-bit

Manufacturer's Datasheet

http://www.ni.com/pdf/manuals/377101b_02.pdf

NI-9215

Range

± 10 V

Sample Rate

100 kS/s

Resolution

16-bit

Manufacturer's Datasheet

http://www.ni.com/pdf/manuals/373779a_02.pdf

Safety Standard

This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use:

  • IEC 61010-1, EN 61010-1

  • UL 61010-1, CSA 61010-1

 

Electromagnetic Compatibility

This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use:

EN 61326 (IEC 61326)

Class A emissions; Basic immunity

EN 55011 (CISPR 11)

Group 1, Class A emissions

AS/NZS CISPR 11

Group 1, Class A emissions

FCC 47 CFR Part 15B

Class A emissions

ICES-001

Class A emissions

CE Compliance

Meets the essential requirements of applicable European Directives, as amended for CE marking, as follows: 2006/95/EC, Low-Voltage Directive (safety); 2004/108/EC, Electromagnetic Compatibility Directive (EMC)

 
 

Environmental

Storage Temperature

-40 °C to 85 °C (-40 °F to 185 °F)

Operating Temperature

-40 °C to 70 °C (-40 °F to 158 °F)

Storage Humidity

5% RH to 95% RH, noncondensing

Operating Humidity

10% RH to 90% RH, noncondensing

Maximum Altitude

5,000 m (16,400 ft)

 