Related Products: |
EGMA-401, EGSA-310, EGSA-320, EGSK-404, EGSK-405, EXMC-001, EXMC-002 |
Related Documents: |
EZDP-2078 |
Type: |
Installation |
Keywords/Labels: |
conduit layout, shaft contact assembly configuration, enclosure specifications |
Summary: |
This article provides the installation planning diagrams for the generator field monitoring system. |
Color on Diagram (next page) |
Conduit Run Description |
Conduit Trade Size |
Max Run Length |
Wire Description |
Purpose |
Wire Supplied By |
Conduit Supplied By |
---|---|---|---|---|---|---|---|
Red |
Shaft Grounding Assembly to Junction Box |
N/A |
3 ft (0.9 m) |
Twisted pair, individually shielded, high temp, 18 AWG + 8 AWG Ground |
Signals and ground from SGA to Junction Box |
Cutsforth |
N/A |
Green |
Junction Box to unit case ground |
N/A |
2 ft (1.5 m) including Red run |
Single conductor, 8 AWG, high temp |
Ground from Junction Box to unit case ground |
Cutsforth |
N/A |
Purple |
Junction Box, through condulet, to monitoring system |
3/4 in. (2 cm) |
27 ft (8.2 m) |
Two high-voltage, CAT6a Ethernet cables |
Signals from Junction Box to monitoring system |
Cutsforth |
Plant Electrical Contractor |
Blue |
Dedicated 120V AC power to monitoring system |
3/4 in. (2 cm) |
N/A |
AC 85-264 V AC, 47-440 Hz, 10 W or DC: 20-32 V DC, 10W 20 A Circuit |
Power for monitoring system |
Plant Electrical Contractor |
Plant Electrical Contractor |
Orange |
Data output to control room |
3/4 in. (2 cm) |
N/A |
CAT6a, shielded, cable tray rated, Ethernet recommended |
Monitoring output to plant’s control room |
Plant Electrical Contractor |
Plant Electrical Contractor |
Yellow (optional) |
Shaft Contact Assembly to monitoring system |
3/4 in. (2 cm) |
80 ft (24.4 m) |
High-voltage, CAT6a Ethernet cable |
Signals from SCA to monitoring system |
Cutsforth |
Plant Electrical Contractor |
Part |
Name |
Part |
Name |
---|---|---|---|
A |
Shaft Rotation Direction |
G |
Signal Wire Disconnect Box |
B |
Shaft Grounding Assembly |
H |
Purple: 3/4 in. (2 cm) conduit from Junction Box to monitoring system |
C |
Cutsforth Shaft Ground Monitoring System |
I |
Orange: 3/4 in. (2 cm) conduit for data output to control room |
D |
Red: Signal and ground cables from SGA to Junction Box |
J |
Blue: 3/4 in. (2 cm) conduit for plant power input |
E |
Junction Box |
K |
[optional] Yellow: 3/4 in. (2 cm) conduit from SCA to monitoring system |
F |
Green: 8 AWG from Junction Box to unit case ground |
-- |
--------------------------------------------------------------------- |
This figure represents a typical layout. Individual installations may vary.
Catalog Number |
Dimensions (in. (mm)) |
Stainless Steel Type |
---|---|---|
CSD16168SS6-MODS |
16.0 (406) x 16.0 (406) x 8.0 (203) |
316 |
Specifications:
|
|
EXMC-001: Optional sunshield for outdoor installations