Related Products: |
EMMK-101, EMMK-102, EMMK-103, EMMC-107, EMMC-108 |
Related Documents: |
EZDP-2056 |
Type: |
Installation |
Keywords/Labels: |
equipment layout, conduit layout |
Summary: |
Instructions and information for installing the EMI Monitoring System enclosure |
This section provides step-by-step instructions for installing the EMI Monitoring System enclosure.
Mount the EMI Monitoring System and Power Supply enclosures at the planned location.
Install the conduit between the EMI Monitoring System enclosure and the Power Supply enclosure.
Install the conduit between the EMI Monitoring System and each HFCT using separate conduit for each HFCT run.
Install the conduit for 120VAC power. Minimum circuit size: 20A 120VAC power supply free of non-linear loads. Consider a circuit with isolated ground.
Install the conduit and wire for data connection. Cutsforth recommends CAT6a or fiber connection.
Color on Diagram |
Conduit Run Description |
Conduit Trade Size* |
Wire Description |
Purpose |
Max. Cable Length |
Wire Supplied By |
---|---|---|---|---|---|---|
Green |
Monitoring System to case ground |
N/A |
Single conductor, 12 AWG |
Enclosure case ground |
20 ft (6.1 m) |
Cutsforth |
Blue |
Monitoring System to Control Room |
3/4 in (2 cm) |
Cat6a Cable |
Data Output to Control Room |
N/A |
Plant Electrical Contractor |
Purple** |
HFCT to Monitoring System |
3/4 in (2 cm) |
RG-223 is preferred |
CT Signal In |
200 ft (61 m) |
Plant Electrical Contractor |
Yellow |
Power Supply Enclosure to Monitoring System |
3/4 in (2 cm) |
Single Twisted-Pair, Shielded, 16 AWG |
DC Power for Monitoring System |
25 ft (7.6 m) |
Cutsforth |
Red |
Plant Power to Power Supply Enclosure |
3/4 in (2 cm) |
120VAC Power (20A dedicated circuit – preferably with isolated ground) |
Power for the Monitoring System |
N/A |
Plant Electrical Contractor |
*Enclosures do not come with conduit holes pre-drilled. Conduit sizing and hole placement is customizable.
**Install each HFCT run in individual conduit runs and do not share conduits so as to avoid any cross talk between CT circuits.
Part |
Name |
Part |
Name |
---|---|---|---|
A |
Cutsforth EMI Monitoring System |
E |
Power Supply Enclosure |
B |
Green: 12 AWG wire for enclosure case ground |
F |
Yellow: 3/4 in (2 cm) conduit from Power Supply Enclosure to monitoring system |
C |
Blue: 3/4 in (2 cm) conduit for data output to control room |
G |
Red: 3/4 in (2 cm) conduit for plant power |
D |
Purple: 3/4 in (2 cm) conduit from HFCT to monitoring system (one conduit run per HFCT) |
Component |
Standard Recommendation |
Recommendation for High-Corrosion Environments |
---|---|---|
Conduit type |
Galvanized rigid metal conduit (RMC) |
Rigid Aluminum Conduit (RAC) |
Conduit fittings type |
Malleable |
Aluminum |
Strut channel type |
Hot-dipped galvanized |
316 Stainless steel |
Mounting hardware |
316 Stainless steel |
316 Stainless steel |
Liquid flexible metallic conduit |
Type HCX |
Type HCX |