Summary: |
Instructions and information for installing the EMI Monitoring System enclosure |
This section provides step-by-step instructions for installing the EMI Monitoring System enclosure.
-
Mount the EMI Monitoring System and Power Supply enclosures at the planned location.
-
Install the conduit between the EMI Monitoring System enclosure and the Power Supply enclosure.
-
Install the conduit between the EMI Monitoring System and each HFCT using separate conduit for each HFCT run.
-
Install the conduit for 120VAC power. Minimum circuit size: 20A 120VAC power supply free of non-linear loads. Consider a circuit with isolated ground.
-
Install the conduit and wire for data connection. Cutsforth recommends CAT6a or fiber connection.
Color on Diagram |
Conduit Run Description |
Conduit Trade Size* |
Wire Description |
Purpose |
Max. Cable Length |
Wire Supplied By |
---|---|---|---|---|---|---|
Green |
Monitoring System to case ground |
N/A |
Single conductor, 12 AWG |
Enclosure case ground |
20 ft (6.1 m) |
Cutsforth |
Blue |
Monitoring System to Control Room |
3/4 in (2 cm) |
Cat6a Cable |
Data Output to Control Room |
N/A |
Plant Electrical Contractor |
Purple** |
HFCT to Monitoring System |
3/4 in (2 cm) |
RG-223 is preferred |
CT Signal In |
200 ft (61 m) |
Plant Electrical Contractor |
Yellow |
Power Supply Enclosure to Monitoring System |
3/4 in (2 cm) |
Single Twisted-Pair, Shielded, 16 AWG |
DC Power for Monitoring System |
25 ft (7.6 m) |
Cutsforth |
Red |
Plant Power to Power Supply Enclosure |
3/4 in (2 cm) |
120VAC Power (20A dedicated circuit – preferably with isolated ground) |
Power for the Monitoring System |
N/A |
Plant Electrical Contractor |
*Enclosures do not come with conduit holes pre-drilled. Conduit sizing and hole placement is customizable.
**Install each HFCT run in individual conduit runs and do not share conduits so as to avoid any cross talk between CT circuits.
Part |
Name |
Part |
Name |
---|---|---|---|
A |
Cutsforth EMI Monitoring System |
E |
Power Supply Enclosure |
B |
Green: 12 AWG wire for enclosure case ground |
F |
Yellow: 3/4 in (2 cm) conduit from Power Supply Enclosure to monitoring system |
C |
Blue: 3/4 in (2 cm) conduit for data output to control room |
G |
Red: 3/4 in (2 cm) conduit for plant power |
D |
Purple: 3/4 in (2 cm) conduit from HFCT to monitoring system (one conduit run per HFCT) |
Component |
Standard Recommendation |
Recommendation for High-Corrosion Environments |
---|---|---|
Conduit type |
Galvanized rigid metal conduit (RMC) |
Rigid Aluminum Conduit (RAC) |
Conduit fittings type |
Malleable |
Aluminum |
Strut channel type |
Hot-dipped galvanized |
316 Stainless steel |
Mounting hardware |
316 Stainless steel |
316 Stainless steel |
Liquid flexible metallic conduit |
Type HCX |
Type HCX |