AGENTS ONLY: This article is locked and visible only to Cutsforth Staff with a Zendesk Agent license.
INTERNAL ONLY: This article is locked and visible only to Cutsforth Staff. External users cannot load this article.
Related Products:
EFMK-101
Related Documents:
EZDP-2064
Type:
Operation
Keywords/Labels:
extrema comparison graph table
Summary:
Describes the ways that extrema comparisons are shown on the RFMS Host app's home screen.
Extrema Value Comparison
In a Table
The Extrema Value Comparison table (5) displays the numeric values of the flux signal extrema detected in the processed flux signal.
Each table row compares a slot (pole B) to its “mirror image” slot (pole A).
Slot shows the slots being compared. For example, the third lag slots for pole B and pole A are “B-3 / A-3”.
Lead/Lag indicates if the slot is Lead or Lag.
Pole B and Pole A show the number of flux values for those poles.
% Diff shows the percent difference between the pole B and pole A values.
Any value above the Shorted Turn Deviation in the Processing settings has a red background.
In Graphs