Related Products:

EGMA-004, EGMA-005, EGMA-006, EGMA-007, EGMA-008, EGMA-013, EGMA-015, EGSA-013, EGSA-015, EGSA-210, EGSA-220

Related Documents:

EZDP-2040

Type:

Installation

Keywords/Labels:

equipment, layout, conduit, wiring

Summary:

Describes the conduits and wiring of the PMS system

Conduit Layout

Color on Diagram

Conduit Run Description

Conduit Trade Size

Wire Qty

Wire Description

Purpose

Wire Supplied By

Blue

SGA to monitoring system

1/2”

1

3 conductors, shielded, 18 AWG, high temp

2 rope wear status, 1 shaft voltage

Cutsforth

Green

SGA to monitoring system

1/2"

1

Single conductor, 8 AWG

Ground from SGA to monitoring system

Cutsforth

Green

Monitoring system to unit case ground

N/A

1

Single conductor, 8 AWG

Ground from monitoring system to unit case ground

Cutsforth

Purple

Plant 120VAC Power to monitoring system

3/4”

1

120VAC Power (20A dedicated circuit, preferably with isolated ground)

Power for the monitoring system

Plant

Black

Plant DCS Drop to monitoring system

2"

7

4/20mA DCS signal lines

Monitoring output to plant’s DCS system

Plant

Yellow*

SCA to monitoring system

1/2"

1

3 conductors, shielded, 18 AWG, high temp

1 rope wear status, 1 shaft voltage, 1 unused

Cutsforth

*Applies only when optional SCA is being installed

Conduit-Layout-Diagram.png