Modbus Interface

Refer to this table when programming the Modbus output on your Brush Condition Monitoring System:

Brush

Name

Value Type

Value Unit

Register Type

Address (Base 1)

Physical Address (Base 0)

Supported Functions

0-229

Sensor Low Batt

boolean

flag

Discrete Input

10000 - 10229

0x000 - 0x0E5

0x02 Read Discrete Input

0-229

Sensor Malfunction

boolean

flag

Discrete Input

10230 - 10459

0x0E6 - 0x1CB

0x02 Read Discrete Input

0-229

Replace Brush Now (Critical)

boolean

flag

Discrete Input

10460 - 10659

0x1CC - 0x2B1

0x02 Read Discrete Input

0-229

Replace Brush Soon (Alert)

boolean

flag

Discrete Input

10690 - 10919

0x2B2 - 0x397

0x02 Read Discrete Input

0-229

High Vibration Warning

boolean

flag

Discrete Input

10920 - 11149

0x398 - 0x47D

0x02 Read Discrete Input

0-229

Sensor Sample Old

boolean

flag

Discrete Input

11150 - 11379

0x47E - 0x563

0x02 Read Discrete Input

0-229

Temperature Critical

boolean

flag

Discrete Input

11380 - 11609

0x564 - 0x649

0x02 Read Discrete Input

0-229

Length Error

boolean

flag

Discrete Input

11610-11839

0x64A - 0x72F

0x02 Read Discrete Input

0-229

Brush Length

short

% remaining

Input Register

30000 - 30229

0x000 - 0x0E5

0x04 Read Input Register

0-229

Pk-to-Pk Displacement

word

0.001 mils

Input Register

30230 - 30459

0x0E6 - 0x1CB

0x04 Read Input Register

0-229

Temperature

short

deg C

Input Register

30460 - 30689

0x1CC - 0x2B1

0x04 Read Input Register

N/A

System Status

word

bitfield: b0 : Hibernation Mode (1 - Enabled, 0 - Disabled) b1-15: RFU

Input Register

330920

0x398

0x04 Read Input Register

N/A

System Time

word

POSIX time (LSB - MSB)

Input Register

30921 - 30922

0x399 - 0x39A

0x04 Read Input Register

N/A

Short Brush Count

word

number of brushes that must be replaced immediately

Input Register

30923

0x39B

0x04 Read Input Register

N/A

Near-Short Brush Count

word

number of brushes that will need replacement soon

Input Register

30924

0x39C

0x04 Read Input Register

N/A

High Vibration Brush Count

word

number of sensors reporting high vibration

Input Register

30925

0x39D

0x04 Read Input Register

N/A

Sensor Error Count

word

number of sensors reporting errors

Input Register

30926

0x39E

0x04 Read Input Register

N/A

Low Battery Total

word

number of sensors reporting low battery

Input Register

30927

0x39F

0x04 Read Input Register

0-229

Battery Voltage

word

mVolts

Input Register

30928 - 31157

0x3A0 - 0x485

0x04 Read Input Register

0-229

RSSI Value

word

decibel milliwatts (dBm)

Input Register

31158 - 31387

0x486 - 0x56B

0x04 Read Input Register

0-229

BHS MAC address (lo byte, little-endian)

word

n/a

Input Register

31388 - 31617

0x56C - 0x651

0x04 Read Input Register

0-229

BHS MAC address (mid byte, little endian)

word

n/a

Input Register

31618 - 31847

0x652 - 0x737

0x04 Read Input Register

0-229

BHS MAC address (hi byte, little-endian)

word

n/a

Input Register

31848 - 32077

0x738 - 0x81D

0x04 Read Input Register

0-229

SensorError Register with Sensor Error Flags

word

n/a

Input Register

32078 - 32307

0x81E - 0x903

0x04 Read Input Register

N/A

Old Samples Count

word

number of sensors reporting old samples

Input Register

32308

0x904

0x04 Read Input Register

N/A

Temperature Critical Count

word

number of sensors reporting critical temperature

Input Register

32309

0x905

0x04 Read Input Register

N/A

Length Error Count

word

Number of sensors reporting brush length errors

Input Register

32310

0x906

0x04 Read Input Register

 

Entering a Static IP Address

  1. Plug the USB keyboard into the BCM system.

  2. Press Alt+F2 to pull up the Application Finder.

    2058-15-1-1.png
  3. Click on the green arrow that is pointed down to display the window of options.

    2058-15-1-2.png
  4. Scroll down, select Network Connections, and click Launch.

    2058-15-1-3.png
  5. Double-click Wired Connection 1.

    2058-15-1-4.png
  6. Select the IPv4 Settings tab.

    2058-15-1-5.png
  7. Under the Method drop-down, select Manual to change IP configuration settings to static.

    2058-15-1-6.png
  8. Click Add.

    2058-15-1-7.png
  9. Enter the desired addressing information, and click Save when you are finished.

    2058-15-1-8.png
 

Locating the MAC Addresses

  1. Connect a USB keyboard to the BCM system.

  2. From the BCM Application Home Screen, press CONFIG in the upper-right corner.

    locating-mac-address-1-2058.png
  3. At the bottom of the Configuration screen, press Advanced Configuration. When prompted, enter the administrative password.

    locating-mac-address-2-2058.png
  4. In the lower-right corner of the Advanced Configuration screen, press Set System Time.

    locating-mac-address-3-2058.png
  5. From the Data & Time screen, press the back button in the upper-left corner.

    locating-mac-address-4-2058.png
  6. From the All Settings menu, select Network.

    locating-mac-address-5-2058.png
  7. The MAC addresses will be listed as “Hardware Address” under each “Ethernet” option in the list on the left hand side.