Related Products: |
EBMA-001, EBMA-002, EBMK-100, EBMK-101, EZBA-001 |
Related Documents: |
EZDP-2058 |
Type: |
Configuration |
Keywords/Labels: |
Programming Modbus Output |
Summary: |
Data to use when programming the Modbus output on your Brush Condition Monitoring System and how to enter a static IP address and locate a MAC address. |
Refer to this table when programming the Modbus output on your Brush Condition Monitoring System:
Brush |
Name |
Value Type |
Value Unit |
Register Type |
Address (Base 1) |
Physical Address (Base 0) |
Supported Functions |
---|---|---|---|---|---|---|---|
0-229 |
Sensor Low Batt |
boolean |
flag |
Discrete Input |
10001 - 10230 |
0x000 - 0x0E5 |
0x02 Read Discrete Input |
0-229 |
Sensor Malfunction |
boolean |
flag |
Discrete Input |
10231 - 10460 |
0x0E6 - 0x1CB |
0x02 Read Discrete Input |
0-229 |
Replace Brush Now (Critical) |
boolean |
flag |
Discrete Input |
10461 - 10690 |
0x1CC - 0x2B1 |
0x02 Read Discrete Input |
0-229 |
Replace Brush Soon (Alert) |
boolean |
flag |
Discrete Input |
10691 - 10920 |
0x2B2 - 0x397 |
0x02 Read Discrete Input |
0-229 |
High Vibration Warning |
boolean |
flag |
Discrete Input |
10921 - 11150 |
0x398 - 0x47D |
0x02 Read Discrete Input |
0-229 |
Brush Length |
short |
% remaining |
Input Register |
30001 - 30230 |
0x000 - 0x0E5 |
0x04 Read Input Register |
0-229 |
Pk-to-Pk Displacement |
word |
0.001 mils |
Input Register |
30231 - 30460 |
0x0E6 - 0x1CB |
0x04 Read Input Register |
0-229 |
Temperature |
short |
deg C |
Input Register |
30461 - 30690 |
0x1CC - 0x2B1 |
0x04 Read Input Register |
0-229 |
Wear Rate |
word |
mils/day |
Input Register |
30691 - 30920 |
0x2B2 - 0x397 |
0x04 Read Input Register |
N/A |
System Status |
word |
bitfield: b0 : Hibernation Mode (1 - Enabled, 0 - Disabled) b1-15: RFU |
Input Register |
330921 |
0x398 |
0x04 Read Input Register |
N/A |
System Time |
word |
POSIX time (LSB - MSB) |
Input Register |
30922 - 30923 |
0x399 - 0x39A |
0x04 Read Input Register |
N/A |
Short Brush Count |
word |
number of brushes that must be replaced immediately |
Input Register |
30924 |
0x39B |
0x04 Read Input Register |
N/A |
Near-Short Brush Count |
word |
number of brushes that will need replacement soon |
Input Register |
30925 |
0x39C |
0x04 Read Input Register |
N/A |
High Vibration Brush Count |
word |
number of sensors reporting high vibration |
Input Register |
30926 |
0x39D |
0x04 Read Input Register |
N/A |
Sensor Error Count |
word |
number of sensors reporting errors |
Input Register |
30927 |
0x39E |
0x04 Read Input Register |
N/A |
Low Battery Total |
word |
number of sensors reporting low battery |
Input Register |
30928 |
0x39F |
0x04 Read Input Register |
0-229 |
Battery Voltage |
word |
mVolts |
Input Register |
30929 - 31158 |
0x3A0 - 0x485 |
0x04 Read Input Register |
0-229 |
RSSI Value |
word |
decibel milliwatts (dBm) |
Input Register |
31159 - 31388 |
0x486 - 0x56B |
0x04 Read Input Register |
0-229 |
BHS MAC address (lo byte, little-endian) |
word |
n/a |
Input Register |
31389 - 31618 |
0x56C - 0x651 |
0x04 Read Input Register |
0-229 |
BHS MAC address (mid byte, little endian) |
word |
n/a |
Input Register |
31619 - 31848 |
0x652 - 0x737 |
0x04 Read Input Register |
0-229 |
BHS MAC address (hi byte, little-endian) |
word |
n/a |
Input Register |
31849 - 32078 |
0x738 - 0x81D |
0x04 Read Input Register |
-
Plug the USB keyboard into the BCM system.
-
Press Alt+F2 to pull up the Application Finder.
-
Click on the green arrow that is pointed down to display the window of options.
-
Scroll down and select Network Connections.
-
Click Launch.
-
Double-click Wired Connection 1.
-
Select the IPv4 Settings tab.
-
Under the Method drop-down, select Manual to change IP configuration settings to static.
-
Click Add.
-
Click Save when you are finished.
-
Connect a USB keyboard to the BCM system.
-
From the BCM Application Home Screen, press CONFIG in the upper-right corner.
-
At the bottom of the Configuration screen, press Advanced Configuration. When prompted, enter the administrative password.
-
In the lower-right corner of the Advanced Configuration screen, press Set System Time.
-
From the Data & Time screen, press the back button in the upper-left corner.
-
From the All Settings menu, select Network.
-
The MAC addresses will be listed as “Hardware Address” under each “Ethernet” option in the list on the left hand side.