Routing Ground Wire, Termination, |
Summary: |
Describes the routing and termination of the ground wire. |
This topic describes the routing and termination of the ground wire.
Drill and tap a 5/16 in - 18 hole 3/4 in (1.90 cm) deep in a suitable grounding location on the outside of the unit case (A) to attach the grounding ring terminal (B). The metal surface to which the grounding ring terminal will be mated must be smooth and free of any paint, rust, oil, or other contaminants that may inhibit the electrical connection. The maximum wire length for the ground run from the Shaft Grounding Assembly to the unit case ground location is 5 ft (1.5 m).