Related Products: |
EGSA-013, EGSA-017 |
Related Documents: |
EZDP-2007 |
Type: |
Installation |
Keywords/Labels: |
Shaft Grounding, Maintenance |
Summary: |
List of routine inspection procedures. |
To ensure that the Shaft Grounding System is in proper working condition, frequently make the following inspections:
Inspect the holder for any signs of wear or damage as well as any excessive build up of dirt or foreign material.
Check for any cracking or breakage of components or welds.
Confirm the “snap in” pressure when installing or removing the rope holder is relatively equal to the other rope holder.
Verify that the meter switch works properly.
Confirm the rope guide is not contacting the shaft. There should be a 1/16 in gap between the rope guide and the face of the shaft.
Inspect the integrity of the rope guide and attachment arms.
Make sure the terminal connection area on the mount is not excessively worn or pitted.