Summary:

Procedure to test for rope wear.

Rope Wear Indicator Test Point

The rope wear indicator test points are connected to the rope status circuitry.

To test for rope wear

  1. Set an oscilloscope or digital voltmeter to read DC voltage.

  2. Place the positive and negative probes on the Rope Wear Indicator “+” and “-“ test points, respectively.

    • A reading between 4.8 V and 5.1V DC indicates that the ropes are in good condition and not in need of replacement.

    • A reading of 0 V DC or fluctuating DC voltages below 4.8 V DC indicate that the ropes should be inspected and the worn rope should be replaced.

Rope_WI_Test_Points.png