Summary: |
Procedure for measuring current flowing to ground from the shaft. |
To measure current flowing to ground from the shaft
Set an oscilloscope or digital voltmeter to measure in the mV scale.
-
Press the button at the bottom of the faceplate to power the current sensor, then place the positive and negative probes on the CURRENT SENSOR + and - test points, respectively.
Use the conversion 100 mV = 1 Amp to convert the read voltage to current, or refer to the following table.