Summary:

Procedure for measuring current flowing to ground from the shaft.

Safety Notices

Ground Current Test Point

To measure current flowing to ground from the shaft

  1. Set an oscilloscope or digital voltmeter to measure in the mV scale.

  2. Press the button at the bottom of the faceplate to power the current sensor, then place the positive and negative probes on the CURRENT SENSOR + and - test points, respectively.

    GCTP.png
    Pushbutton_Test_Point.png

    Use the conversion 100 mV = 1 Amp to convert the read voltage to current, or refer to the following table.