Summary: |
Information on alternate ground wire locations. |
The turbine case is the preferred grounding location. The ground conductor should run the shortest route possible, up to a maximum of 47 ft.
NOTE
Do not run the ground wire an excessive distance in an attempt to terminate to an existing grounding pad. A short run is the best run.
Grounding to the generator case is an alternate option that should be used if it facilitates a shorter overall ground run. However, it typically results in a much noisier ground reference and may introduce unwanted interference, especially when measuring with a handheld oscilloscope.
Junction box
Remote Meter Point or Assurance Monitoring System