Related Products:

EGSK-301, EGMA-301

Related Documents:

EZDP-2044

Type:

Planning Guide

Keywords/Labels:

Assurance Monitoring, Shaft Grounding, Diagram, Conduit

Summary:

Table and diagram detailing the correct set up of conduit runs with specifications for conduit trade size, run lengths, and wire.

Conduit Layout and Maximum Cable Lengths

Color on Diagram

Conduit Run Description

Conduit Trade Size

Max Run Length

Wire Description

Purpose

Wire Supplied by

Conduit Supplied by

Red

Shaft Grounding Assembly to junction box

1/2 in (1.27 cm)

27 ft (8.2 m)

3 conductors, shielded, 18 AWG, high temp

2 rope wear status, 1 shaft voltage,

Cutsforth

Plant Electrical Contractor

Purple

Junction box to assurance system

3/4 in (2 cm)

30 ft (9.1 m) (including Red run)

4 twisted pair, individually shielded, 18 AWG

Signal wires from junction box to assurance system

Cutsforth

Plant Electrical Contractor

Green

Junction box to unit case ground

N/A

47 ft (14.3 m)(including Red run)

8 AWG copper MTW green

Ground from junction box to unit case ground

Cutsforth

Plant Electrical Contractor

Black

Assurance to unit case ground

N/A

9 ft (2.7 m)

20 AWG coaxial RG58

Signal ground from assurance system to unit case ground

Cutsforth

Plant Electrical Contractor

Blue

Dedicated 120 V AC power to assurance system

3/4 in (2 cm)

N/A

AC: 85–264 V AC, 47–440 Hz, 10 W or DC: 20–32 V DC, 10W

Power for assurance system

Plant Electrical Contractor

Plant Electrical Contractor

Orange

Plant DCS drop to assurance system

1-1/4 in (3.17 cm)

N/A

4–20 mA DCS signal lines

Monitoring output to plant’s DCS system

Plant Electrical Contractor

Plant Electrical Contractor

Yellow

High-Frequency Drain

N/A

4 ft 6 in (1 m 15 cm)

12 AWG, chemical-resistant wire

Drain ground wire for high-frequency voltage spikes

Cutsforth

Plant Electrical Contractor

2044-new_6-3__Series_2_.svg
A - Red: 1/2 in (1.27 cm) conduit from SGA to junction box E - Black: 20 AWG coaxial RG58 to unit case ground
B - Yellow: 12 AWG from main ground conductor, through resistor, then to case ground F - Blue: 3/4 in (2 cm) conduit for plant power input
C - Green: 8 AWG from junction box to unit case ground G - Orange: 1-1/4 in (3.17 cm) conduit for 4–20 mA lines
D - Purple: 3/4 in (2 cm) conduit from junction box to Assurance Monitoring System  