Summary: |
Generator conditions that must be established for a successful installation. |
The shaft must be fully coupled.
The generator and turbine bearing caps in the load compartment must be fully installed.
The condition of the shaft at the Shaft Grounding Assembly installation location must be documented by photo or video. If the shaft is still rotating, use a strobe to capture a video of the shaft condition. To facilitate a robust electrical contact for the shaft grounding system, make sure that the shaft surface is free of grooving, pitting, oxidation, and contamination.