Premium Monitoring System, Ground Current, Troubleshooting, Shaft Grounding |
Summary: |
Technical information on solving issues with application such as malfunctioning sensors or loss of ground. |
If any LIVE values remain constant for a period of 10 seconds or longer, check the Premium Monitoring System for a possible frozen application or malfunctioning sensor. If the application reports an error, see Application Errors | Premium Monitoring System.
If the unit is online, but Channel 6 is transmitting 4 mA (indicating that generator is offline), check the Shaft Grounding Assembly for a loss of ground. For example, check the rope-to-shaft connection for any oil, dust, or other contaminants that may interfere with the electrical connection.