Related Products: |
EGMA-004, EGMA-005, EGMA-006, EGMA-007, EGMA-008, EGMA-013, EGMA-015, EGMA-016, EGMA-019 |
Related Documents: |
EZDP 2020 and 2038 |
Type: |
Technical information |
Keywords/Labels: |
Premium Monitoring System, Signal Cables |
Summary: |
This article includes recommendations for signal runs and voltage measurements as well as background information on the type of wire used in the signal cables. |
Cutsforth recommends that signal runs be 40 ft (12 m) or less whenever possible. If longer runs are chosen, we do not guarantee what level of signal quality may be obtained. Longer runs have been functional for plants where tradeoffs were understood. Within reason, longer runs may provide the information needed to monitor basic grounding integrity and provide low-level waveform information.