Summary: |
This article contains considerations to investigate a possible fault indication involving the grounding current stepping up. |
If a significant step down in grounding current takes place in conjunction with an increase in shaft voltage, inspect the grounding assembly, grounding rope, and shaft surface for potential deterioration of the grounding rope-to-shaft connection.
Average and/or Peak-to-Peak Grounding Current Steps Down
Average or Peak-to-Peak Shaft Voltages or Grounding Currents Step Up
Average or Peak-to-Peak Shaft Voltages or Currents Trending Up or Down Over Time